Remarks | UK importer address: Signify Commercial UK Limited, 3, Guildford Business Park, GU2 8XG
|
Application code | EII
|
Type version | mk2
|
Lamp type | TL5/PL-L
|
Number of lamps | 1
piece/unit
|
Number of products on MCB (16 A type B) (nom.) | 12
|
Automatic restart | Yes
|
Input Voltage | 220 to 240
V
|
Input frequency | 50 to 60
Hz
|
Operating frequency (max.) | 105
kHz
|
Operating frequency (min.) | 45
kHz
|
Ignition method | Programmed Start
|
Crest factor (max.) | 1.7
|
Power factor 100% load (nom.) | 0.97
|
Ignition time (max.) | 0.2
s
|
Mains voltage performance (AC) | -8%-+6%
|
Mains voltage safety (AC) | -10%-+10%
|
Earth leakage current (max.) | 0.5
mA
|
Inrush current width | 0.40
ms
|
Power losses (nom.) | 7
W
|
Inrush current peak (max.) | 45
A
|
Connector type input terminals | WAGO 251 universal connector
[ Suitable for both automatic wiring (ALF and ADS) and manual wiring] |
Connector type output terminals | WAGO 251 universal connector
[ Suitable for both automatic wiring (ALF and ADS) and manual wiring] |
Connector type control input terminals | WAGO 251 universal connector
[ Suitable for both automatic wiring (ALF and ADS) and manual wiring] |
Wire strip length | 8.0-9.0
mm
|
Dual fixture master/slave | Not applicable
[ Master/Slave oper. not applicable] |
Control input terminal cross section | 0.50-1.00
mm²
|
Input terminal cross section | 0.50-1.00
mm²
|
Output terminal cross section | 0.50-1.00
mm²
|
Auto-insert (ALF/ADS) wire cross section | 0.5
mm²
|
Rated ballast-lamp power | 80 W
|
T-ambient (max.) | 50
°C
|
T-ambient (min.) | 10
°C
|
T storage (max.) | 80
°C
|
T storage (min.) | -25
°C
|
Stable lamp operation temperature | Not Specified
|
T-Ignition (max.) | 50
°C
|
T-Ignition (min.) | 0
°C
|
Control interface | 1-10V
|
Regulating level power | 1%-100%
|
Control input protection | Yes (Basic insulation)
|
Housing | L 360x30x21
|
Battery voltage lamp ignition | 196
V
|
Battery voltage lamp operation | 154-276
|
Energy efficiency index | A1 BAT
|
IP classification | IP 20
[ Ingress Protection 20] |
EMI 9 kHz ... 30 MHz | EN55015
|
EMI 30 MHz ... 1,000 MHz | EN55022 level B
|
Safety standard | IEC 61347-2-3
|
Performance standard | IEC 60929
|
Quality standard | ISO 9000:2000
|
Environmental standard | ISO 14001
|
Harmonic current emission standard | IEC 61000-3-2
|
EMC immunity standard | IEC 61547
|
Vibration standard | IEC68-2-6 F c
|
Bumps standard | IEC 68-2-29 Eb
|
Humidity standard | EN 61347-2-3 clause 11
|
Approval marks | CE marking
|
Temperature marking | Yes
|
Emergency standard | IEC 60598-2-22
|
Humming and noise level | Inaudible
|
Full product code | 871150091011030
|
Order product name | HF-R 180 TL5/PL-L EII 220-240V 50/60Hz
|
EAN/UPC – product | 8711500910110
|
Order code | 91011030
|
Local order code | HFR180TL5/PLL
|
Numerator – quantity per pack | 1
|
Numerator – packs per outer box | 12
|
SAP material | 913700609066
|
SAP net weight (piece) | 0.285
kg
|