HF-Regulator Intelligent Touch DALI for TL5/TL-D/PL-L lamps

HF-Ri TD 1 14/21/24/39 E+

  • Dimming the next step in energy saving

    Product information

    Downloads

    Leaflet
    Size:430.0 kB

    See all downloads

Videos

[trigger to render Video Gallery]

Images

Specifications Show all

General Information
Application code
E+
Type version
mk2
Lamp type
TL5
Number of lamps
1 piece/unit
Number of products on MCB (16 A type B) (nom.)
30
Automatic restart
Yes
Operating and Electrical
Input voltage
195-240 V
Input frequency
50-60 Hz
Operating frequency (max.)
110 kHz
Operating frequency (min.)
45 kHz
Ignition method
Warm Start
Crest factor (max.)
1.7
Power factor 100% load (nom.)
0.95
Ignition time (max.)
1 s
Mains voltage performance (AC)
-8%-+6%
Mains voltage safety (AC)
-10%-+10%
Earth leakage current (max.)
0.5 mA
Inrush current width
0.23 ms
Standby power consumption (max.)
0.25 W
Ballast factor (nom.)
1
Power losses (nom.)
3.4 W
Inrush current peak (max.)
16.5 A
Wiring
Connector type input terminals
WAGO 251 universal connector  [ Suitable for both automatic wiring (ALF and ADS) and manual wiring]
Cable capacity output wires mutual (max.)
200 pF
Connector type output terminals
WAGO 251 universal connector  [ Suitable for both automatic wiring (ALF and ADS) and manual wiring]
Connector type control input terminals
WAGO 251 universal connector  [ Suitable for both automatic wiring (ALF and ADS) and manual wiring]
Wire strip length
8.0-9.0 mm
Dual fixture master/slave
Yes  [ Master/Slave operation possible]
Control input terminal cross section
0.50-1.00 mm²
Input terminal cross section
0.50-1.00 mm²
Output terminal cross section
0.50-1.00 mm²
Auto Insert (ALF/ADS) Wire Cross Section
0.75 mm²
Cable capacity output wires to earth (max.)
200 pF
System characteristics
Rated ballast-lamp power
14/21/24/39 W
Rated lamp power on TL-D
36 W
System power on TL-D
35.7 W
Lamp power on TL-D
32 W
Power loss on TL-D
3.7 W
Rated lamp power on PL-L
24/36/40 W
System power on PL-L
25.9/33.7/41.9 W
Lamp power on PL-L
22.5/30.0/38.0 W
Power loss on PL-L
3.4/3.7/3.9 W
Rated lamp power on TL5
14/21/24/39 W
System power on TL5
16.6/23.9/26.5/40.3 W
Lamp power on TL5
13.7/20.7/23.0/36.5 W
Power loss on TL5
2.9/3.2/3.5/3.8 W
Rated lamp power on TL5 ECO
13/19/20/34 W
System power on TL5 ECO
15.4/22.2/23.2/36.7 W
Lamp power on TL5 ECO
12.5/19.1/20.0/33.0 W
Power loss on TL5 ECO
2.9/3.1/3.2/3.7 W
Temperature
T ambient (max.)
50 °C
T ambient (min.)
-25 °C
T storage (max.)
80 °C
T storage (min.)
-40 °C
T case lifetime (max.)
75 °C
T-Case maximum (max.)
75 °C
Stable lamp operation temperature
15°C
T-Ignition (max.)
50 °C
T-Ignition (min.)
-25 °C
Controls and Dimming
Control interface
TD
Regulating level power
1%-100%
Control input protection
Yes (Basic insulation)
Mechanical and Housing
Housing
L 360x30x21
Emergency Operation
Battery voltage lamp ignition
198-254 V
Battery voltage lamp operation
176-254
Approval and Application
Energy efficiency index
A1 BAT
EMI 9 kHz... 30 MHz
EN55015
EMI 30 MHz... 1,000 MHz
EN 55022 Class B
Safety standard
IEC 61347-2-3
Performance standard
IEC 60929
Quality standard
ISO 9000:2000
Environmental standard
ISO 14001
Harmonic current emission standard
IEC 61000-3-2
EMC immunity standard
IEC 61547
Vibration standard
IEC68-2-6 F c
Bumps standard
IEC 68-2-29 Eb
Humidity standard
EN 61347-2-3 clause 11
Approval marks
CE marking
ENEC certificate
VDE-EMV certificate
Temperature marking
Yes
Emergency standard
IEC 60598-2-22
Humming and noise level
Inaudible
Product Data
Full product code
871829169689600
Order product name
HF-Ri TD 1 14/21/24/39 E+
EAN/UPC – product
8718291696896
Order code
69689600
Local Code
HFRITD11439T5PL
Numerator – quantity per pack
1
Numerator – packs per outer box
12
Material no. (12NC)
913700698366
Net weight (piece)
0.261 kg
Installation Diagrams
HF-Ri TD 1 14/21/24/39 TL5 E+
Performance Diagrams

Recently Viewed

    • Manage your projects with MyProjects
      Use MyProjects to create, save manage and share items and projects with you colleagues and team members.

Events    

 

 

Smart Buildings

19.10.2016, Birmingham NEC

Presentation: ‘Connected Lighting for Offices - Beyond Illumination’ by Darren Smith
 

Grand Designs Live

Find us on Stand L190, Technology Zone,
Hall 5

19-23.10.2016, Birmingham NEC

Highway Electrical Association (HEA)
Annual Conference
03.11.2016, Celtic Manor, Newport

WORKTECH 2016

9-10.11.2016, Canary Wharf, London
 

View all events

You are now visiting our Global professional lighting website, visit your local website by going to the USA website