HF-Regulator Intelligent Touch DALI for PL-T/C and TL5C

HF-Ri TD 160 TL5C E+ 195-240V 50/60Hz

HF-Ri TD 160 TL5C E+ 195-240V 50/60Hz

  • Dimming – a next step in energy saving.

    Product information

Videos

[trigger to render Video Gallery]

Images

Specifications Show all

General Information
Application code
E+
Type version
-
Lamp type
TL5C
Number of lamps
1 piece/unit
Number of products on MCB (16 A type B) (nom.)
12
Automatic restart
Yes
Operating and Electrical
Input voltage
195-240 V
Input frequency
50-60 Hz
Operating frequency (max.)
66 kHz
Operating frequency (min.)
45 kHz
Ignition method
Warm Start
Crest factor (max.)
1.7
Power factor 100% load (nom.)
0.95
Ignition time (max.)
0.6 s
Mains voltage performance (AC)
176-275V
Mains voltage safety (AC)
154-276V
Earth leakage current (max.)
0.5 mA
Inrush current width
0.35 ms
Standby power consumption (max.)
0.27 W
Ballast factor (nom.)
1
Power losses (nom.)
4.0 W
Inrush current peak (max.)
45 A
Wiring
Connector type input terminals
WAGO 250 series
Cable capacity output wires mutual (max.)
150 pF
Connector type output terminals
WAGO 250 series
Connector type control input terminals
WAGO 250 series
Wire strip length
8.0-9.0 mm
Dual fixture master/slave
Yes  [ Master/Slave operation possible]
Control input terminal cross section
0.50-1.50 mm²
Input terminal cross section
0.50-1.50 mm²
Output terminal cross section
0.50-1.50 mm²
Auto Insert (ALF/ADS) Wire Cross Section
0.50-1.50 mm²
Cable capacity output wires to earth (max.)
150 pF
System characteristics
Rated ballast-lamp power
60 W
Rated lamp power on TL5C
60 W
System power on TL5C
64 W
Power loss on TL5C
4 W
Lamp power on TL5C
60 W
Temperature
T ambient (max.)
50 °C
T ambient (min.)
-25 °C
T storage (max.)
80 °C
T storage (min.)
-40 °C
T case lifetime (max.)
75 °C
T-Case maximum (max.)
75 °C
Stable lamp operation temperature
15°C
T-Ignition (max.)
50 °C
T-Ignition (min.)
-25 °C
Controls and Dimming
Control interface
TD
Regulating level power
3%-100%
Control input protection
Yes (Basic insulation)
Mechanical and Housing
Housing
L123X79X33
Emergency Operation
Battery voltage lamp ignition
198-254 V
Battery voltage lamp operation
176-275
Approval and Application
Energy efficiency index
A1 BAT
EMI 9 kHz... 30 MHz
EN55015
Safety standard
IEC 61347-2-3
Performance standard
IEC 60929
Quality standard
Not Specified
Environmental standard
-
Harmonic current emission standard
Not Specified
EMC immunity standard
IEC 61547
Vibration standard
IEC68-2-6 F c
Bumps standard
IEC 68-2-29 Eb
Humidity standard
EN 61347-2-3 clause 11
Approval marks
EMC
CE marking
ENEC certificate
Temperature marking
Yes
Emergency standard
IEC 60598-2-22
Humming and noise level
24 dB(A)
Product Data
Full product code
871829171862800
Order product name
HF-Ri TD 160 TL5C E+ 195-240V 50/60Hz
EAN/UPC – product
8718291718628
Order code
71862800
Numerator – quantity per pack
1
Numerator – packs per outer box
12
Material no. (12NC)
913700761966
Net weight (piece)
0.200 kg
Installation Diagrams
HF-Ri TD 1 26-42 PL-T/C E+

Recently Viewed

    • Manage your projects with MyProjects
      Use MyProjects to create, save manage and share items and projects with you colleagues and team members.

Events    

 

 

Business Climate Summit

28-29.06.2016, London Guildhall

 

The Public Sector Show

28.06.2016, ExCeL

 

Grand Designs Live

19-23.10.2016, Birmingham NEC

 

View all events

You are now visiting our Global professional lighting website, visit your local website by going to the USA website