HF-Regulator II for TL5 lamps

HF-R 2 14-35 TL5 EII 220-240V 50/60Hz

HF-R 2 14-35 TL5 EII 220-240V 50/60Hz

  • Product Description

    Product information

    Downloads

    Leaflet
    Size:537.6 kB

    See all downloads

Videos

[trigger to render Video Gallery]

Images

Specifications Show all

General Information
Application code
EII
Type version
MK1
Lamp type
TL5
Number of lamps
2 piece/unit
Number of products on MCB (16 A type B) (nom.)
12
Automatic restart
Yes
Operating and Electrical
Input voltage
220 to 240 V
Input frequency
50-60 Hz
Operating frequency (max.)
100 kHz
Operating frequency (min.)
46 kHz
Ignition method
Programmed Start
Crest factor (max.)
1.7
Power factor 100% load (nom.)
0.98
Ignition time (max.)
0.2 s
Mains voltage performance (AC)
-8%-+6%
Mains voltage safety (AC)
-10%-+10%
Earth leakage current (max.)
0.5 mA
Inrush current width
0.40 ms
Power losses (nom.)
5.3-6.5 W
Inrush current peak (max.)
45 A
Wiring
Connector type input terminals
WAGO 251 universal connector  [ Suitable for both automatic wiring (ALF and ADS) and manual wiring]
Connector type output terminals
WAGO 251 universal connector  [ Suitable for both automatic wiring (ALF and ADS) and manual wiring]
Connector type control input terminals
WAGO 251 universal connector  [ Suitable for both automatic wiring (ALF and ADS) and manual wiring]
Wire strip length
8.0-9.0 mm
Dual fixture master/slave
-  [ not specified]
Control input terminal cross section
0.50-1.00 mm²
Input terminal cross section
0.50-1.00 mm²
Output terminal cross section
0.50-1.00 mm²
Auto Insert (ALF/ADS) Wire Cross Section
0.5 mm²
System characteristics
Rated ballast-lamp power
14-35 W
Temperature
T ambient (max.)
50 °C
T ambient (min.)
-20 °C
T storage (max.)
80 °C
T storage (min.)
-25 °C
Stable lamp operation temperature
-
T-Ignition (max.)
50 °C
T-Ignition (min.)
0 °C
Controls and Dimming
Control interface
1-10V
Regulating level power
1%-100%
Control input protection
Yes (Basic insulation)
Mechanical and Housing
Housing
L360X30X21
Emergency Operation
Battery voltage lamp ignition
196 V
Battery voltage lamp operation
154-276
Approval and Application
Energy efficiency index
A1
EMI 9 kHz... 30 MHz
EN55015
EMI 30 MHz... 1,000 MHz
EN55022LEVELB
Safety standard
IEC 61347-2-3
Performance standard
IEC60929
Quality standard
ISO 9000:2000
Environmental standard
ISO14001
Harmonic current emission standard
IEC61000-3-2
EMC immunity standard
IEC 61547
Vibration standard
IEC68-2-6FC
Bumps standard
IEC 68-2-29 Eb
Humidity standard
EN61347-2-3CLAUSE11
Approval marks
CE marking
ENEC certificate
VDE-EMV certificate
Temperature marking
Yes
Emergency standard
IEC 60598-2-22
Humming and noise level
Inaudible
Product Data
Full product code
871150091178030
Order product name
HF-R 2 14-35 TL5 EII 220-240V 50/60Hz
EAN/UPC – product
8711500911780
Order code
91178030
Local Code
HFR21435TL5EII
Numerator – quantity per pack
1
Numerator – packs per outer box
12
Material no. (12NC)
913700619566
Net weight (piece)
0.290 kg
Installation Diagrams
HF-R 2 lamps TL5/PL-L/TL-D
Performance Diagrams

Recently Viewed

    • Manage your projects with MyProjects
      Use MyProjects to create, save manage and share items and projects with you colleagues and team members.

Events    

 

 

Business Climate Summit

28-29.06.2016, London Guildhall

 

The Public Sector Show

28.06.2016, ExCeL

 

Grand Designs Live

19-23.10.2016, Birmingham NEC

 

View all events

You are now visiting our Global professional lighting website, visit your local website by going to the USA website